48V100Ah

The shock-absorbing buffer material should be filled between the batteries; the outer package should be firm enough, waterproof, and have a certain degree of heat insulation; the inside of the package should be filled with buffer material so as to prevent the battery from colliding and causing safety accident during transportation. At the same time, the battery should be half-full during transportation.
Availability:
Quantity:
  • NE-48D100-NP

  • Headway


Li ion Battery Specification

UPS Power Supplier

NE-48D100-NP

Overview:

Welcome to use the “Headway” Li-ion battery. The battery is a high performance li ion battery with independent intellectual property rights and developed by our company. Please read the manual carefully to make he equipment perform battery and longer cycle life. The manual provides important installation and operating instructions.

The product is based on the lithium iron phosphate battery, through the reliable BMS system and high-performance balanced technology, the product has the characteristic of flexible configuration and high reliability. The product is widely used in distributed energy, power grid energy storage, photovoltaic energy storage, data room and other applications.

 

1. Battery Specification

Category

Item

Parameter

Nominal parameter

Nominal Voltage(V)

48


Nominal Capacity(Ah)

100

structure parameter

Weight(kg)

~ 52


Dimension(mm)

L442*W410*H220mm(5U)

Electrical performance parameters

Nominal Capacity(AH)

100Ah


Rated Voltage(V)

48 V


Overvoltage alarm value(can be set)

54.75 V


Overvoltage alarm recovery value(can be set)

51 V


Overvoltage protection value(can be set)

57 V


Under-voltage alarm value(can be set)

45 V


Under-voltage alarm recovery value(can be set)

46.5 V


Under-voltage protection value(can be set)

42.5 V


Rated power(Wh)

4.8kWH


Max charging voltage(can be set)

58 V


cut-off discharge voltage(can be set)

42.5 V


Max charging current(can be set)

100A


Max continuous output current(can be set)

100A

Other parameter

Operating temperature

-10-55℃


Service life

≥5 years


cycle life

≥2000 times